Generator Service
GPR has been supplying, repairing, overhauling and servicing generator sets from 500 watts to one megawatt since 1965. Our One Stop Shop is a fully equipped generator division that has complete lifting capabilities (ten ton), a steam clean bay, temperature controlled ovens, a vacuum impregnation system, a dynamic balancing stand and an in-house machining and welding shop with factory trained journeyman electricians and heavy duty mechanics.
-
24 hour call out service
-
On-site maintenance programs
-
Mobile load banks
-
Complete in-house overhauls
-
Regular stock of the more common breakdown items
Diesel Generators
GPR is the fastest growing Perkins distributor in Western Canada. We have committed to a large inventory of skid mount generator packages and complete engines and parts. Perkins (powerpart) gives GPR access to over 50,000 parts and exchange units.
Liquid/Natural Gas Generators
Custom built natural gas and propane gensets. A long history with Lister Natural Gas and now a partnership with Ford Industrial completes GPR’s ability to offer a comprehensive product line of quality diesel and natural gas power generation packages.
Generator windings are often exposed to the elements and can be very contaminated. Performing regular maintenance with steam cleaning, baking, installing new bearings and re-varnishing the windings may add years of trouble free life to your prime power or standby generator set.
In-House Generator Overhaul
Includes:
-
Dismantling generator
-
Steam clean
-
Bake
-
Test all windings
-
Mic bearing housings and shaft surface
-
Replace bearings (labour only)
-
Test diodes c.t.s. etc.
-
Epoxy windings
-
Assemble
Does not include:
-
Uncouple and re-couple to engine
-
Electrical wiring disconnect and reconnect
-
Mechanical repairs
-
Parts
-
Balancing
-
Electronic testing – a.v.r. (automatic voltage regulators under frequency protection)
Call to review standard per kilowatt pricing.
On-Site Generator Planned Maintenance (Electrical)
Recommended 5,000 Hour Service
-
Check overall appearance of equipment and controls
-
Check internal connections
-
Meggar and/or Hi-Pot test – main: stator/rotor – exciter: stator/rotor
-
Surge/surge comparison test – main: stator/rotor – exciter: stator/rotor
-
Check excitation system (diodes), surge suppressors, etc.
-
Clean and check batteries
-
Check battery charging system
-
Check operation of cooling thermostats and louvers
-
Check building air filters (shack and building)
-
Check output voltage, frequency and amperage
-
Adjust/calibrate analog gauges
Recommended 10,000 Hour Service
-
All checks performed on the 5,000 hour Service
-
Check transfer switching system
-
Back end bearing change and measure mic surfaces
-
Load test
The cost of the 10,000 hour service can be accurately estimated after the 5,000 hour visit.